Description
The 3-phase Conex Trailer Mounted 50 KVA UPS system is ready to go when you need it. This trailer accepts a 3-phase input voltage of 480VAC or a single-phase input voltage of 120VAC. The output voltage of the trailer is 120VAC, single-phase. Designed with 4 strings of 12VDC, VRLA batteries the 50kVA provides approximately 68 minutes of runtime at 40KW.
Our rental fleet of over 30 trailers are ready to deploy within two hours of your call. UPS Rental powered by Sure Power has technicians on call 24x7x365 to meet our customer’s demands, no matter your location. Whether our customers need an emergency UPS Rental or a complete customized battery system, Sure Power’s team is ready to respond. Sure Power is up to the challenge of meeting our customer’s critical demands.
Trailer Data: | |
---|---|
Manufacturer: | Connex Trailer |
Total Length: | 25.25’L x 8’W x 12.5’H |
Total Weight – Trailer and Contents: | 25,000 lbs. |
UPS Information: | |
Manufacturer: | Emerson/Liebert |
Series/Model: | EXCOR Apodys/120-50KNT-120-1-PWM |
kVA Rating | 50kVA |
Output Power Factor: | 0.8 |
Output KW Rating: | 40KW |
Input Voltage: | 480 or 208 VAC |
Input Wiring: | 3W + Ground Dual Input: 480 VAC, 3Ø and 120 VAC, 1Ø 100 Amps UPS Input and 425 Amp Bypass Inpu |
Output Voltage: | 120VAC L-N, 1Ø |
Output Wiring: | 2W + Ground 417 Amps Maximum Output Capacity |
Wrap-Around Maintenance Bypass: | Yes |
UPS Battery Information: | |
Manufacturer: | Bard |
Number of A/C Units: | 2 |
Capacity Per Unit: | 3 Tons |
Total Tonnage: | 6 Tons |
Monitoring Information: | |
HVAC Supervision | Ambient Temperature | Discrete UPS Alarms Cellular Alarm Monitoring |
|
* Spare Batteries and Spare Parts Onboard |